100 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 148. Basic Parameters — P1, continued
Code Parameter Min. Max. Unit Default ID Note
P1.11
Hand Control Place 0 1695 0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Fieldbus
P1.12

Hand Reference 6 136 0 = AI1
1 = AI2
2 = Slot A: AI1
3 = Slot B: AI1
4 = AI1 Joystick
5 = AI2 Joystick
6 = Keypad
7 = Fieldbus Ref
9 = Max Frequency
10 = AI1 + AI2
11 = AI1 - AI2
12 = AI2 - AI1
13 = AI1 * AI2
14 = AI1 or AI2
15 = MIN(AI1,AI2)
16 = MAX(AI1,AI2)
17 = PID1 Control Output
18 = PID2 Control Output
P1.13
Auto 1 Control Place 0 135 0 = I/O Terminal Start 1
1 = Fieldbus
2 = I/O Terminal Start 2
3 = Keypad
P1.14

Auto 1 Reference 1 137 See Par ID 136
P1.15
Auto 2 Control Place 1 138 See Par ID 135
P1.16

Auto 2 Reference 7 139 See Par ID 136
Table 149. Basic Setting — P2.1
Code Parameter Min. Max. Unit Default ID Note
P2.1.1

Damper Start 0 483 0 = Normal
1 = Interlock Start
2 = Interlock Tout
3 = Interlock Delay
P2.1.2

Damper Time Out 1 32500 s 5 484
P2.1.3

Damper Delay 1 32500 s 5 485
P2.1.4
AI Ref Scale Min Value 0.00 See Par ID 145 Hz 0.00 144
P2.1.5
AI Ref Scale Max Value See Par ID 144 400.00 Hz 0.00 145
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.