Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Table 34. Analog Output 1 — P3.3
Code Parameter Min. Max. Unit Default ID Note
P3.3.1
AO1 Mode 0 227 See Par ID 222
P3.3.2
AO1 Function 1 146 0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed (0-Nom)
4 = Motor Current (0-Nom)
5 = Motor Torque (0-Nom)
6 = Motor Power (0-Nom)
7 = Motor Voltage (0-Nom)
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (-2-+2N)
22 = Motor Torque (-2-+2N)
23 = Motor Power (-2-+2N)
24 = PT100 Temperature
33 = SlotA PT100 Temp Channel 1
34 = SlotA PT100 Temp Channel 2
35 = SlotA PT100 Temp Channel 3
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = User Defined Output
40 = Motor Current (-2-+2N)
P3.3.3
AO1 Minimum 1 149 0 = 0V / 0 mA
1 = 2V / 4 mA
P3.3.4
AO1 Filter Time 0.00 10.00 s 1.00 147
P3.3.5
AO1 Scale 10 1000 % 100 150
P3.3.6
AO1 Inversion 0 148 See Par ID 181
P3.3.7
AO1 Offset -100.00 100.00 % 0.00 173
Table 35. Analog Output 2 — P3.4
Code Parameter Min. Max. Unit Default ID Note
P3.4.1
AO2 Mode 0 228 See Par ID 222
P3.4.2
AO2 Function 4 229 See Par ID 146
P3.4.3
AO2 Minimum 1 232 See Par ID 149
P3.4.4
AO2 Filter Time 0.00 10.00 s 1.00 230
P3.4.5
AO2 Scale 10 1000 % 100 233
P3.4.6
AO2 Inversion 0 231 See Par ID 181
P3.4.7
AO2 Offset -100.00 100.00 % 0.00 234
Drive Control
Table 36. Basic Setting — P4.1
Code Parameter Min. Max. Unit Default ID Note
P4.1.1
Keypad Reference See Par ID 101 See Par ID 102 Hz 0.00 141
P4.1.2
Keypad Direction 0 116 0 = Forward
1 = Reverse
P4.1.3
Keypad Stop 1 114 0 = Enabled-Keypad Operation
1 = Always Enabled
P4.1.4
Hand Key Enable 0 1724 0 = Enabled
1 = Disabled
P4.1.5
Reverse Enable 1 1679 0 = Disabled
1 = Enabled
P4.1.6 Change PhaseSequence
Motor
0 2515 0 = Change Disable
1 = Change Enable
otes:N
Parameter value will be set to be default when changing macros.