Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Table 48. FB Process Data Output Sel — P12.2, continued
Code Parameter Min. Max. Unit Default ID Note
P12.2.10
Standard Status Word Bit1 Function Select 2 2416 See Par ID 2415
P12.2.11
Standard Status Word Bit2 Function Select 3 2417 See Par ID 2415
P12.2.12
Standard Status Word Bit3 Function Select 4 2418 See Par ID 2415
P12.2.13
Standard Status Word Bit4 Function Select 5 2419 See Par ID 2415
P12.2.14
Standard Status Word Bit5 Function Select 6 2420 See Par ID 2415
P12.2.15
Standard Status Word Bit6 Function Select 7 2421 See Par ID 2415
P12.2.16
Standard Status Word Bit7 Function Select 8 2422 See Par ID 2415
RS485 Bus
Table 49. Basic Setting — P12.3.1
Code Parameter Min. Max. Unit Default ID Note
P12.3.1.1
RS485 Comm Set 0 586 0 = Modbus RTU
1 = BACnet MS/TP
Table 50. Modbus RTU — P12.3.2
Code Parameter Min. Max. Unit Default ID Note
P12.3.2.1
Slave Address 1 247 1 587
P12.3.2.2
Baud Rate 1 584 0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 115200
P12.3.2.3
Parity Type 2 585 0 = None
1 = Odd
2 = Even
P12.3.2.4 Modbus RTU Protocol Status 588 0 = Initial
1 = Stopped
2 = Operational
3 = Faulted
P12.3.2.5 Comm Timeout Modbus RTU 0 60000 ms 10000 593
P12.3.2.6 Modbus RTU Fault Response 2516 0 = in Fieldbus Control
1 = in all Control
Table 51. BACnet MS/TP — P12.3.3
Code Parameter Min. Max. Unit Default ID Note
P12.3.3.1
MSTP Baud Rate 2 594 0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P12.3.3.2
MSTP Device Address 0 127 1 595
P12.3.3.3
MSTP Instance Number 0 4194302 Varies 596
P12.3.3.4 MSTP Comm Timeout 0 60000 ms 10000 598
P12.3.3.5 MSTP Protocol Status 599 0 = Stopped
1 = Operational
2 = Faulted
P12.3.3.6 MSTP Fault Code 600 0 = None
1 = Sole Master
P12.3.3.7
MSTP Fault Response 0 2526 See Par ID 2516
P12.3.3.8
MSTP Max Master 127 1537
otes:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.