107POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 156. Supervisions — P3.2, continued
Code Parameter Min. Max. Unit Default ID Note
P3.3.3
AO1 Minimum 1 149 0 = 0V / 0 mA
1 = 2V / 4 mA
P3.3.4
AO1 Filter Time 0.00 0.00 s 1.00 147
P3.3.5
AO1 Scale 1010%100 150
P3.3.6
AO1 Inversion 0 148 See Par ID 181
P3.3.7
AO1 Offset -100.00 -100.00 % 0.00 173
Table 157. Analog Output 2 — P3.4
Code Parameter Min. Max. Unit Default ID Note
P3.4.1
AO2 Mode 0 228 See Par ID 222
P3.4.2
AO2 Function 4 229 See Par ID 146
P3.4.3
AO2 Minimum 1 232 See Par ID 149
P3.4.4
AO2 Filter Time 0.00 10.00 s 1.00 230
P3.4.5
AO2 Scale 10 1000 % 100 233
P3.4.6
AO2 Inversion 0 231 See Par ID 181
P3.4.7
AO2 Offset -100.00 100.00 % 0.00 234
Table 158. Logic Function — P3.5
Code Parameter Min. Max. Unit Default ID Note
P3.5.1
Logic Function Select 0 751 0 = AND
1 = OR
2 = XOR
P3.5.2
Logic Operation Input A 0 752 0 = Not Used
1 = Ready
2 = Run
3 = Fault
6 = Reversed
7 = Warning
8 = Zero Frequency
9 = Control from I/O
14 = Run Bypass/Drive
16 = In Bypass Mode
17 = At Speed
18 = Auto Control
19 = Freq Limit 1 Superv
20 = Freq Limit 2 Superv
22 = PID1 Superv
23 = PID2 Superv
24 = OverHeat Fault
28 = 4mA Ref Fault/Warning
29 = OverCurrent Regular
30 = OverVoltage Regular
31 = UnderVoltage Regular
32 = Torq Limit Superv
33 = Ref Limit Superv
34 = Un-Requested Rotation
Direction
35 = Thermal Fault/Warning
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.