147
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P2.4.6 181 AI1 Signal Invert 1,2,3 RW
This parameter is used to invert the logic of the analog input.
0 No Inversion = no inversion of analog Vin signal takes place. 0V/0(4)mA = min frequency,
10V/20mA = max frequency
1 Inverted = inversion of analog signal takes place. 0V/0(4)mA = max frequency, 10V/20mA = min frequency.
Figure 43. AI1 No signal inversion
Output
Frequency
P2.22
P2.21
0
100%
AI1
(Term. 2)
P2.4/2.14P2.3/2.13
P2.2/2.12 = 0
AI1 = 0 – 100%
P2.2/2.12 = 1
AI1 = Custom
Figure 44. AI1 Signal Inversion
Output
Frequency
P2.22
P2.21
0
100%
AI1
(Term. 2)
P2.4/2.14
P2.3/2.13
P2.2/2.12 = 0
AI1 = 0 – 100%
P2.2/2.12 = 1
AI1 = Custom
Maximum AI1 signal = minimum set speed.
Minimum AI1 signal = maximum set speed.
P2.4.7 178 AI1 Joystick Hyst 3 RW
This parameter is used to set the analog joystick control hysteresis around the 0 speed reference. To ignore
values around the 0 speed reference, set the value greater then 0%, this will cause a +/- dead band around
the low analog reference. With an analog signal at 0+/- this value the reference will stay at 0Hz or min
speed.
Figure 45. Example of joystick hysteresis
Frequency Reference
Hz
Reference
Scaling Max
P2.22= 70 Hz
Max Freq.
P1.2 = 50 Hz
Min Freq. P1.1 =
Ref. Scaling Min
P2.21 = 0 Hz
P2.3/2.13
= 20%
P2.4/2.14
= 90%
Joystick Hysteresis,
P2.7 = 20%
REVERSE
50%
FORWARD
50%
From Reverse to Forward
From Forward to Reverse
Analog
Input (V/mA)
(0 – 10V/20 mA)
A
B