99POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 144. Timer/Interval Control — M7
Code Parameter Min. Max. Unit Default ID Note
M7.1 TC1, TC2, TC3 558
M7.2 Interval 1 559 0 = Inactive
1 = Active
M7.3 Interval 2 560 See Par ID 559
M7.4 Interval 3 561 See Par ID 559
M7.5 Interval 4 562 See Par ID 559
M7.6 Interval 5 563 See Par ID 559
M7.7 Timer 1 s 0 569
M7.8 Timer 2 s 0 571
M7.9 Timer 3 s 0 573
Table 145. User Defined Output — M8
Code Parameter Min. Max. Unit Default ID Note
M8.1 Output Varies 2445
M8.2 Reference Varies 2447
Table 146. MWH Monitor — M9
Code Parameter Min. Max. Unit Default ID Note
M9.1 Total MWh Count Mwh 601
M9.2 Total Power Day Count 603
M9.3 Total Power Hr Count 606
M9.4 Trip MWh Count Mwh 604
M9.5 Trip Power Day Count 636
M9.6 Trip Power Hr Count 637
M9.7 Total Run Time Count 2827
M9.8 Number of Starts 2830
M9.9 Trip Run Time Count 2829
Table 147. Multi-Monitoring — M11
Code Parameter Min. Max. Unit Default ID Note
M11.1 Multi-Monitoring 1, 2, 3 30
Parameters
Table 148. Basic Parameters — P1
Code Parameter Min. Max. Unit Default ID Note
P1.1
Min Frequency 0.00 See Par ID 102 Hz 0.00 101
P1.2
Max Frequency See Par ID 101 400.00 Hz Varies 102
P1.3
Accel Time 1 0.1 3000.0 s 20.0 103
P1.4
Decel Time 1 0.1 3000.0 s 20.0 104
P1.5
Motor Nom Current DriveNomCurrCT*1/10 DriveNomCurrCT*2 A DriveNomCurrCT 486
P1.6
Motor Nom Speed 300 20000 rpm Varies 489
P1.7
Motor PF 0.30 1.00 0.85 490
P1.8
Motor Nom Voltage 180 690 V Varies 487
P1.9
Motor Nom Frequency 8.00 400.00 Hz Varies 488
P1.10
HOA Source 0 2465 0 = I/O Terminal/
Keypad/Fieldbus
1 = Keypad
2 = IO Terminal
3 = Fieldbus
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.