46
Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Table 42. Drive — P6.2
Code Parameter Min. Max. Unit Default ID Note
P6.2.1
Line Start Lockout 2 750 0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P6.2.2
Fault Reset Start 0 2483 0 = Start/Stop After Fault Reset
1 = Restart After Fault Reset
P6.2.3
4mA Input Fault 0 306 0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P6.2.4
4mA Fault Frequency 0.00 See Par ID 102 Hz 0.00 331
P6.2.5
External Fault 2 307 See Par ID 308
P6.2.6
Input Phase Fault 2 332 See Par ID 308
P6.2.7
Uvolt Fault Response 2 330 See Par ID 308
P6.2.8
Unit Under Temp Prot 2 1564 See Par ID 308
P6.2.9
RTC Fault 1 955 See Par ID 308
P6.2.10
Replace Battery Fault
Response
1 1256 See Par ID 308
P6.2.11
Replace Fan Fault Response 1 1257 See Par ID 308
P6.2.12
Cold Weather Mode 0 2126 See Par ID 1679
P6.2.13
Cold Weather Volt. Level 0.0 20.0 % 2.0 2127
P6.2.14
Cold Weather Time Out 0 10 min 3 2128
P6.2.15 Cold Weather Password 2129
P6.2.16 Under Temp Fault Override 2130 See Par ID 2118
P6.2.17
STO Fault Response 2 2427 0 = No Action
1 = Warning
2 = Fault
P6.1.18
Preheat Control Source 31 2160 0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
31 = Drive Temperature
32 = SlotA PT100 Temp Channel 1
33 = SlotA PT100 Temp Channel 2
34 = SlotA PT100 Temp Channel 3
otes:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.