108 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 158. Logic Function — P3.5, continued
Code Parameter Min. Max. Unit Default ID Note
P3.5.2
Logic Operation Input A 0 752 36 = Bypass Enable
37 = Jog Speed Select
38 = Motor Therm Protection
39 = FB Digital Input 1
40 = FB Digital Input 2
41 = FB Digital Input 3
42 = FB Digital Input 4
43 = Damper Control
44 = TC1 Status
45 = TC2 Status
46 = TC3 Status
48 = Power Limit Superv
49 = Temp Limit Superv
50 = Analog Input Superv
56 = Logic Fulfilled
P3.5.3
Logic Operation Input B 0 753 See Par ID 752
Drive Control
Table 159. Basic Setting — P4.1
Code Parameter Min. Max. Unit Default ID Note
P4.1.1
Keypad Reference See Par ID 101 See Par ID 102 Hz 0.00 141
P4.1.2
Keypad Direction 0 116 0 = Forward
1 = Reverse
P4.1.3
Keypad Stop 1 114 0 = Enabled-Keypad Operation
1 = Always Enabled
P4.1.4
Hand Key Enable 0 1724 0 = Enabled
1 = Disabled
P4.1.5
Reverse Enable 1 1679 See Par ID 1346
P4.1.6 Change PhaseSequence Motor 0 2515 0 = Change Disable
1 = Change Enable
P4.1.7
Power Up HOA Select 0 1685 0 = Hold Last
1 = Hand Control
2 = Auto control
3 = Off
P4.1.8
Bumpless Enable 0 2462 See Par ID 1346
P4.1.9
Run Delay Time 0 32500 s 0 2423
P4.1.10
Start Mode 0 252 0 = Ramp
1 = Flying Start
P4.1.11
Stop Mode 0 253 0 = Coasting
1 = Ramp
P4.1.12
Ramp 1 Shape 0.0 10.0 s 0.0 247
P4.1.13
Ramp 2 Shape 0.0 10.0 s 0.0 248
P4.1.14
Accel Time 2 0.1 3000.0 s 10.0 249
P4.1.15
Decel Time 2 0.1 3000.0 s 10.0 250
P4.1.16
Power Loss Function 0 267 See Par ID 1346
P4.1.17
Power Loss Time 0.3 5.0 s 2.0 268
P4.1.18

2nd Stage Ramp Frequency See Par ID 101 See Par ID 102 Hz 30.00 2444
P4.1.19
Run Remove Stop Mode 0 2667 See Par ID 253
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.