123POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 199. Timer — P11.6
Code Parameter Min. Max. Unit Default ID Note
P11.6.1
Timer 1 Duration 0 72000 s 0 511
P11.6.2
Timer 1 Channel 0 532 See Par ID 519
P11.6.3
Timer 2 Duration 0 72000 s 0 513
P11.6.4
Timer 2 Channel 0 533 See Par ID 519
P11.6.5
Timer 3 Duration 0 72000 s 0 515
P11.6.6
Timer 3 Channel 0 534 See Par ID 519
Communication
Table 200. FB Process Data Input Sel — P12.1
Code Parameter Min. Max. Unit Default ID Note
P12.1.1
FB Process Data Input 1 Sel 0 2560 0 2533
P12.1.2
FB Process Data Input 2 Sel 0 2560 2542 2534
P12.1.3
FB Process Data Input 3 Sel 0 2560 2550 2535
P12.1.4
FB Process Data Input 4 Sel 0 2560 103 2536
P12.1.5
FB Process Data Input 5 Sel 0 2560 104 2537
P12.1.6
FB Process Data Input 6 Sel 0 2560 107 2538
P12.1.7
FB Process Data Input 7 Sel 0 2560 0 2539
P12.1.8
FB Process Data Input 8 Sel 0 2560 0 2540
Table 201. FB Process Data Output Sel — P12.2
Code Parameter Min. Max. Unit Default ID Note
P12.2.1
FB Process Data Output 1 Sel 1 1556
P12.2.2
FB Process Data Output 2 Sel 2 1557
P12.2.3
FB Process Data Output 3 Sel 3 1558
P12.2.4
FB Process Data Output 4 Sel 4 1559
P12.2.5
FB Process Data Output 5 Sel 5 1560
P12.2.6
FB Process Data Output 6 Sel 6 1561
P12.2.7
FB Process Data Output 7 Sel 7 1562
P12.2.8
FB Process Data Output 8 Sel 28 1563
P12.2.9
Standard Status Word Bit0
Function Select
1 2415 0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
11 = PID1 Superv
12 = PID2 Superv
13 = OverHeat Fault
14 = OverCurrent Regular
15 = OverVoltage Regular
16 = UnderVoltage Regular
17 = 4mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
Direction
24 = Thermistor Fault Output
25 = Fire Mode
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.