Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P2.2.1 143 1 = Para ID 190: DI closed contact = start /open contact = stop Para ID 191: DI closed contact = reverse / open
contact = forward - This would be considered 2 wire control with a contact on start/stop, contact open it
stops and direction on 2nd start signal.
1,2,3 RW
24V+
DIN1 20
DIN2 21
CMA 24
GND 12
ID190 - Start Signal: DigIN:1 ID143 Start Stop Logic: Start/Stop
ID191- Start Signal 2: DigIN:2 ID143 Start Stop Logic: Forward/Reverse
15
Figure 32. Start, stop and reverse
FWD
REV
DIN1
DIN2
Output
Frequency
Stop Function
(P7.10) = Coasting
t
otes:N
The first selected direction has the highest priority.
When the DIN1 contact opens the direction of rotation starts to change.
If Start forward (DIN1) and Start reverse (DIN2) signals are active
simultaneously the Start forward signal (DIN1) has priority.
2 = Para ID 190: DI closed contact = start / open contact = stop Para ID 191: DI closed contact = start enabled
/ open contact = start disabled and drive stopped if running Motor direction keeps forward - This would
be considered 3 wire control with Start signal 2 required to be closed to enable Start on Start signal 1.
24V+
DIN1 20
DIN2 21
CMA 24
GND 12
ID190 - Start Signal: DigIN:1 ID143 Start Stop Logic: Start/Stop
ID191- Start Signal 2: DigIN:2 ID143 Start Stop Logic: Forward/Reverse
15