75POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Table 91. Auto Restart — P6.4
Code Parameter Min. Max. Unit Default ID Note
P6.4.1
AR Wait Time 1.00 300.00 s 1.00 321
P6.4.2
AR Trail Time 0.00 600.00 s 30.00 322
P6.4.3
AR Start Function 0 323 0 = Flying Start
1 = Ramp
P6.4.4
Undervoltage Attempts 0 10 1 324
P6.4.5
OverVoltage Attempts 0 10 1 325
P6.4.6
OverCurrent Attempts 0 3 1 326
P6.4.7
4mA Fault Attempts 0 10 1 327
P6.4.8
Motor Temp Fault
Attempts
010 1329
P6.4.9
External Fault Attempts 0 10 0 328
P6.4.10
Underload Attempts 0 10 1 336
P6.4.11
OP Cont Interlock
Attempts
010 02803
PID Controller 1
Table 92. Basic Setting — P7.1
Code Parameter Min. Max. Unit Default ID Note
P7.1.1
PID1 Control Gain 0.00 200.00 % 100.00 1294
P7.1.2
PID1 Control ITime 0.00 600.00 s 1.00 1295
P7.1.3
PID1 Control DTime 0.00 100.00 s 0.00 1296
P7.1.4

PID1 Process Unit 0 1297 0 = %
1 = 1/min
2 = rpm
3 = ppm
4 = pps
5 = l/s
6 = l/min
7 = l/h
8 = kg/s
9 = kg/min
10 = kg/h
11 = m3/s
12 = m3/min
13 = m3/h
14 = m/s
15 = mbar
16 = bar
17 = Pa
18 = kPa
19 = mVS
20 = kW
21 = °C
22 = GPM
23 = gal/s
24 = gal/min
25 = gal/h
26 = lb/s
27 = lb/min
28 = lb/h
29 = CFM
30 = ft3/s
31 = ft3/min
32 = ft3/h
33 = ft/s
34 = in wg
35 = ft wg
36 = PSI
37 = lb/in2
38 = HP
39 = °F
ote:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.