117POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 178. Feedforward 1 — P7.5.2
Code Parameter Min. Max. Unit Default ID Note
P7.5.2.1

PID1 Feedforward 1 Source 0 1340 0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = FB Process Data Input 1
6 = FB Process Data Input 2
7 = FB Process Data Input 3
8 = FB Process Data Input 4
9 = FB Process Data Input 5
10 = FB Process Data Input 6
11 = FB Process Data Input 7
12 = FB Process Data Input 8
13 = PT100 Temperture
14 = PID2 Output
15 = SlotA PT100 Temp Channel 1
16 = SlotA PT100 Temp Channel 2
17 = SlotA PT100 Temp Channel 3
18 = SlotB PT100 Temp Channel 1
19 = SlotB PT100 Temp Channel 2
20 = SlotB PT100 Temp Channel 3
21 = FB PID1 Feedforward 1
22 = FB PID1 Feedforward 2
P7.5.2.2
PID1 Feedforward 1 Min -200.00 200.00 % 0.00 1341
P7.5.2.3
PID1 Feedforward 1 Max -200.00 200.00 % 100.00 1342
Table 179. Feedforward 2 — P7.5.3
Code Parameter Min. Max. Unit Default ID Note
P7.5.3.1

PID1 Feedforward 2 Source 0 1343 See Par ID 1340
P7.5.3.2
PID1 Feedforward 2 Min -200.00 200.00 % 0.00 1344
P7.5.3.3
PID1 Feedforward 2 Max -200.00 200.00 % 100.00 1345
PID Controller 2
Table 180. Basic Setting — P8.1
Code Parameter Min. Max. Unit Default ID Note
P8.1.1
PID2 Control Gain 0.00 200.00 % 100.00 1356
P8.1.2
PID2 Control I Time 0.00 600.00 s 1.00 1357
P8.1.3
PID2 Control D Time 0.00 100.00 s 0.00 1358
P8.1.4

PID2 Process Unit 0 1359 See Par ID 1297
P8.1.5
PID2 Process Unit Min -99999.99 See Par ID 1362 Varies 0.00 1360
P8.1.6
PID2 Process Unit Max See Par ID 1360 99999.99 Varies 100.00 1362
P8.1.7
PID2 Process Unit Decimal 0 4 2 1364
P8.1.8

PID2 Error Inversion 0 1365 See Par ID 181
P8.1.9
PID2 Dead Band 0.00 99999.99 Varies 0.00 1366
P8.1.10
PID2 Dead Band Delay 0.00 320.00 s 0.00 1368
P8.1.11
PID2 Ramp Time 0.00 300.00 s 0.00 1373
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.