98 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 142. FB Monitor Menu — M5, continued
Code Parameter Min. Max. Unit Default ID Note
M5.4 Application Status
Word
29 Bit 0 = MC_Ready
Bit 1 = MC_Run
Bit 2 = MC_Fault or Fault Trip
Bit 3 = FB_Ref_Active
Bit 4 = MC_Stopping
Bit 5 = MC_Reverse
Bit 6 = MC_Warning or AR
Bit 7 = MC_ZeroSpeed
Bit 8 = IO Control Indicator
Bit 9 = Panel Control Indicator
Bit 10 = Panel Fieldbus Control Indicator
Bit 11 = MC_DC_Brake
Bit 12 = RunEnable
Bit 13 = Run Bypass
Bit 14 = External Brake Control
Bit 15 = In Bypass Mode
M5.5 Standard Status
Word
2414 Bit 0 = See PAR ID 2415 (default = Ready)
Bit 1 = See PAR ID 2416 (default = Run)
Bit 2 = See PAR ID 2417 (default = Fault)
Bit 3 = See PAR ID 2418 (default = Fault Invert)
Bit 4 = See PAR ID 2419 (default = Warning)
Bit 5 = See PAR ID 2420 (default = Reversed)
Bit 6 = See PAR ID 2421 (default = At Speed)
Bit 7 = See PAR ID 2422 (default = Zero Frequency)
Bit 8 - 15 = Not Used
M5.6 FB Status Word 2101 Bit 0 = Ready
Bit 1 = Run
Bit 2 = Direction
Bit 3 = Fault
Bit 4 = Warning
Bit 5 = At reference
Bit 6 = Bypass
M5.7 FB Control Word 2001 Bit 0 = Run_Stop
Bit 1 = Forward_Rev
Bit 2 = FaultReset
Bit 3 = FB input data 1
Bit 4 = FB input data 2
Bit 5 = FB input data 3
Bit 6 = FB input data 4
Bit 7 = Bypass
Bit 8 = FB_Ctrl
Bit 9 = FB_Ref
M5.8 FB Speed Reference 2003
Table 143. PID Monitor — M6
Code Parameter Min. Max. Unit Default ID Note
M6.1 PID1 Set Point Varies 16
M6.2 PID1 Feedback Varies 18
M6.3 PID1 Error Value Varies 20
M6.4 PID1 Output % 22
M6.5 PID1 Status 23 0 = Stopped
1 = Running
2 = Sleep Mode
M6.6 PID2 Set Point Varies 32
M6.7 PID2 Feedback Varies 34
M6.8 PID2 Error Value Varies 36
M6.9 PID2 Output % 38
M6.10 PID2 Status 39 See Par ID 23