112 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 166. Drive — P6.2, continued
Code Parameter Min. Max. Unit Default ID Note
P6.2.3
4mA Input Fault 0 306 0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P6.2.4
4mA Fault Frequency 0.00 See Par ID 102 Hz 0.00 331
P6.2.5
External Fault 2 307 See Par ID 308
P6.2.6
Input Phase Fault 2 332 See Par ID 308
P6.2.7
Uvolt Fault Response 2 330 See Par ID 308
P6.2.8
Unit Under Temp Prot 2 1564 See Par ID 308
P6.2.9
RTC Fault 1 955 See Par ID 308
P6.2.10
Replace Battery Fault
Response
1 1256 See Par ID 308
P6.2.11
Replace Fan Fault
Response
1 1257 See Par ID 308
P6.2.12
Cold Weather Mode 0 2126 See Par ID 1346
P6.2.13
Cold Weather Volt. Level 0.0 20.0 % 2.0 2127
P6.2.14
Cold Weather Time Out 0 10 min 3 2128
P6.2.15 Cold Weather Password 2129
P6.2.16 Under Temp Fault Override 2130 See Par ID 2118
P6.2.17
STO Fault Response 2 2427 0 = No Action
1 = Warning
2 = Fault
P6.2.18 Warning Operation Mode 2657 0 = No Action
1 = Warning, Do not Store data
2 = Warning, Store data
P6.2.19 Fan Protection 2664
P6.2.20 Under Voltage Trip Level 2666
P6.2.21 OP Cont Interlock
Protection
2831
Table 167. Communication — P6.3
Code Parameter Min. Max. Unit Default ID Note
P6.3.1
Fieldbus Fault Response 2 334 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
4 = Warning, Coast
P6.3.2
OPTCard Fault Response 2 335 See Par ID 308
P6.3.3
IP Address Confliction
Resp
1 1678 See Par ID 308
P6.3.4
Keypad Comm Fault
Response
2 2157 See Par ID 308
Table 168. Auto Restart — P6.4
Code Parameter Min. Max. Unit Default ID Note
P6.4.1
AR Wait Time 1.00 300.00 s 1.00 321
P6.4.2
AR Trail Time 0.00 600.00 s 30.00 322
P6.4.3
AR Start Function 0 323 0 = Flying Start
1 = Ramp
P6.4.4
Undervoltage Attempts 0 10 1 324
P6.4.5
OverVoltage Attempts 0 10 1 325
P6.4.6
OverCurrent Attempts 0 3 1 326
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.