140
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P2.2.19 194 Run Enable 1,2,3 RW
Use this parameter for setting external safety start input that is required along with start command for
frequency converter to turn on output. When using this command if the function is set for Normally Open,
the drive will see this as a open input and not allow the drive to run due to no Ready. The default state being
Normally Closed indicates that the drive is in a Ready condition and will accept the start command. When
assigned to one of the DIGIN or Time channels it requires the input to be high to activate output. Can be
set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot,
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows for having
an input turn on without having to hard wire it to the physical
relay output.
Closed contact = Start of motor enabled
Open contact = Start of motor disabled
P2.2.20 205 Preset Speed B0 1,2,3 RW
Use this parameter selecting the of the digital input for an external speed setpoint desired. Validating 3
digital inputs will allow for 7 preset speeds to be obtained. When switching between inputs it will follow
the acceleration and deceleration time. When all the inputs are set to Normally Open none of the preset
speeds will be enabled and the output will follow the control place reference command. If the function is set
for Normally Closed the drive will follow the preset speed assigned to the inputs enabled. When assigned to
one of the DIGIN on the control board or an installed option card it is looking for a high input to enable that
preset. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board
inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function
allows for having an input turn on without having to hard wire it to the physical relay output.
P2.2.21 206 Preset Speed B1 1,2,3 RW
Use this parameter selecting the of the digital input for an external speed setpoint desired. Validating 3
digital inputs will allow for 7 preset speeds to be obtained. When switching between inputs it will follow
the acceleration and deceleration time. When all the inputs are set to Normally Open none of the preset
speeds will be enabled and the output will follow the control place reference command. If the function is set
for Normally Closed the drive will follow the preset speed assigned to the inputs enabled. When assigned to
one of the DIGIN on the control board or an installed option card it is looking for a high input to enable that
preset. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board
inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function
allows for having an input turn on without having to hard wire it to the physical relay output.
P2.2.22 207 Preset Speed B2 1,2,3 RW
Use this parameter selecting the of the digital input for an external speed setpoint desired. Validating 3
digital inputs will allow for 7 preset speeds to be obtained. When switching between inputs it will follow
the acceleration and deceleration time. When all the inputs are set to Normally Open none of the preset
speeds will be enabled and the output will follow the control place reference command. If the function is set
for Normally Closed the drive will follow the preset speed assigned to the inputs enabled. When assigned to
one of the DIGIN on the control board or an installed option card it is looking for a high input to enable that
preset. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board
inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function
allows for having an input turn on without having to hard wire it to the physical relay output.
Figure 36. Activation of fixed frequencies
f
(Hz)
DI3
DI4
DI1
15 Hz
10 Hz
5 Hz
0 Hz
B0 B0B0
B1B1
FWD
t (s)