126 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 207. BACnet IP — P12.4.3
Code Parameter Min. Max. Unit Default ID Note
P12.4.3.1

BACnet IP UDP port number 47808 1733 47808 = BAC0
47809 = BAC1
47810 = BAC2
47811 = BAC3
47812 = BAC4
47813 = BAC5
47814 = BAC6
47815 = BAC7
47816 = BAC8
47817 = BAC9
47818 = BACA
47819 = BACB
47820 = BACC
47821 = BACD
47822 = BACE
47823 = BACF
P12.4.3.2
BACnet IP Foreign Device 0 1734 See Par ID 1346
P12.4.3.3
BACnet IP BBMD IP 0.0.0.0 1735
P12.4.3.4
BACnet IP BBMD Port 47808 1737 See Par ID 1733
P12.4.3.5
BACnet IP Registration
Interval
065535 10 1738
P12.4.3.6
BACnet IP Comm Timeout 0 60000 0 1739
P12.4.3.7 BACnet IP Protocol Status 1740 See Par ID 599
P12.4.3.8
BACnet IP Fault Behavior 0 1741 See Par ID 2516
P12.4.3.9
BACnetIP Instance Number 0 4194302 Varies 1742
System
Table 208. Basic Setting — P13.1
Code Parameter Min. Max. Unit Default ID Note
P13.1.1 Language 0 340 0 = English
1 = ѝ᮷
2 = Deutsch
P13.1.2
Application 142 0 = Basic
1 = PID
2 = Advanced
P13.1.3
Parameter Sets 619 0 = No
1 = Reload Defaults
2 = Reload Set 1
3 = Reload Set 2
4 = Store Set 1
5 = Store Set 2
6 = Reset
7 = Reload Defaults VM
P13.1.4 Up To Keypad 620 See Par ID 2118
P13.1.5
Down From Keypad 621 0 = No
1 = All Parameters
2 = All, No Motor
3 = App Parameters
P13.1.6 Parameter Comparison 623 0 = No
1 = Compare with Keypad
2 = Compare with Default
3 = Compare with Set 1
4 = Compare with Set 2
P13.1.7 Password 0 9999 0 624
P13.1.8 Parameter Lock 0 625 0 = Change Enable
1 = Change Disable
P13.1.9 Multimonitor Set 0 627 See Par ID 625
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.