Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P6.2.2 2483 Fault Reset Start 1,2,3 RW
This parameter is used to defines how the drive would start after a Fault Reset is given if the run command is
still present to the device.
0 - Start/Stop After Fault Reset - run command has to be cycled to restart after fault reset.
1 - Restart After Fault Reset - run command is still active after fault the drive will restart without
resendingcommand.
P6.2.3 306 4mA Input Fault 1,2,3 RW
Use this parameter to set the device reaction after occurring of “4-20mA fault”. This fault could be device
dependent. Theinformation can also be programmed into digital output DO1 or relay outputs RO1 andRO2.
0 = No response
1 = Warning
2 = Warning, the frequency from 10 seconds back is set as reference
3 = Warning, the Preset Frequency Para ID331 is set as reference
4 = Fault, stop mode after fault according to standard stop mode.
5 = Fault, stop mode after fault always by coasting
P6.2.4 331 4mA Fault Frequency 1,2,3 RW
Use this parameter to set the preset frequency for the 4-20mA fault condition. See Para ID306 = 3.
P6.2.5 307 External Fault 1,2,3 RW
Use this parameter to set the device reaction after occurring an “External Fault”. This failure could be device
dependent. The status information can also be programmed into digital output DO1 and into relay outputs
RO1 and RO2.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting
P6.2.6 332 Input Phase Fault 1,2,3 RW
Use this parameter to set the device reaction to a “Phase Loss” fault condition. This failure could be
devicedependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting
P6.2.7 330 Uvolt Fault Response 1,2,3 RW
Use this parameter to set the device reaction to a “UnderVoltage Mains” fault condition. This failure could
be device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting
P6.2.8 1564 Unit Under Temp Prot 1,2,3 RW
This parameter used to set the reaction when a “Undertemperature Device” condition occurres. This failure
could be device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode.
3 = Fault, stop mode
P6.2.9 955 RTC Fault 1,2,3 RW
This parameter sets the device reaction after a “Realtime Clock Fault” condition has occurred. This condition
could be possible device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting
P6.2.10 1256 Replace Battery Fault Response 1,2,3 RW
This parameter sets the device reaction after a “Replace Battery” condition has occurred, when the battery
falls below 2V level. This condition could be possible device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting