Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P8.1.6 1362 PID2 Process Unit Max 2,3 RW
This parameter is used to defines the maximum process unit value for the PID controller.
P8.1.7 1364 PID2 Process Unit Decimal 2,3 RW
This parameter is used to defines the amount of decimal places used in the value for the PID Controller
setpoint.
P8.1.8 1365 PID2 Error Inversion 2,3 RW
This parameter defines the way the process value output reacts to the feedback signal.
0 = Normal, If feedback is less than set-point, PID controller output increases.
1 = Inverted, If feedback is less than set-point, PID controller output decreases.
P8.1.9 1366 PID2 Dead Band 2,3 RW
This parameter sets the PID Dead band around the set point in process units. This is a band where no
actions occur to the output of the PID controller, to prevent oscillation or repeated activation/deactivation of
controller.
P8.1.10 1368 PID2 Dead Band Delay 2,3 RW
This parameter sets the delay time, if the PID process value goes out of the Dead Band area for the desired
time delay at that point the controller will re-initialize and try to level out again.
P8.1.11 1373 PID2 Ramp Time 2,3 RW
This parameter defines the rising and falling ramp times for changes in the process value setpoint. The ramp
time corresponds to the time it takes to change the setpoint value from minimum to the maximum, if the
value is 0 no ramps are used.
P8.2.1 2546 FB PID2 Set Point 1 2,3 RW
PID Set point1 value from Network. Can be assigned to PID2 Set Point Source.
P8.2.2 2548 FB PID2 Set Point 2 2,3 RW
PID Set point2 value from Network. Can be assigned to PID2 Set Point Source.
P8.2.3 2552 FB PID2 Feedback 1 2,3 RW
PID Feedback value1 from Network. Can be assigned to PID2 Feedback Source.
P8.2.4 2553 FB PID2 Feedback 2 2,3 RW
PID Feedback value2 from Network. Can be assigned to PID2 Feedback Source.
P8.2.5 2556 FB PID2 Feedforward 1 2,3 RW
PID Feedforward value1 from Network. Can be assigned to PID2 Feedforward Source.
P8.2.6 2557 FB PID2 Feedforward 2 2,3 RW
PID Feedforward value2 from Network. Can be assigned to PID2 Feedforward Source.
P8.3.1.1 1369 PID2 Keypad Set Point 1 2,3 RW
This parameter sets the Keypad PID Reference value set point 1.
P8.3.1.2 1371 PID2 Keypad Set Point 2 2,3 RW
This parameter sets the Keypad PID Reference value set point 2.
P8.3.1.3 2467 PID2 Wake Up Action 2,3 RW
Use this parameter to define the wakeup function action. This defines if a static absolute value is used above
or below the level setting or a relative value that changes based off the set point value.
0: Wakeup when below wakeup level (Absolute Level)
1: Wakeup when above wakeup level (Absolute Level)
2: Wakeup when below wakeup level % from PID set point (Relative setpoint)
3: Wakeup when above wakeup level % from PID set point (Relative setpoint)
P8.3.1.4 2662 PID2 Sleep Boost level 2,3 RW
PID2 Sleep boost level, range shall be [-9999,9999], unit shall be PID unit. Default value shall be 0.
P8.3.1.5 2663 PID2 Sleep Boost Max Time 2,3 RW
PID2 Sleep boost maximum time, range shall be [1,300] seconds. Default value shall be 30s.