186
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P8.3.3.5 2399 PID2 Set Point 2 Sleep Unit Sel 2,3 RW
Use this parameter to define the variable used when going into the sleep mode.
0 = Output Frequency
1 = Motor Speed
2 = Motor Current
3 = PID1 Feedback
P8.3.3.6 2456 PID2 Set Point 2 Sleep Level 2,3 RW
Use this parameter to set the level of which the unit value is used to look at to go into the sleep mode. When
the unit drops below or goes above this level for the sleep delay time it will put the drive into the sleep mode.
P8.3.3.7 1388 PID2 Set Point 2 Sleep Delay 2,3 RW
Use this parameter sets the minimum time after the variable drops below the Sleep level for this amount of
time that the output will shutoff.
P8.3.3.8 1389 PID2 Set Point 2 WakeUp Level 2,3 RW
Use this parameter to set the level for the drive wakes up form the sleep mode condition. This level is
variable based off the wake up action selection.
P8.3.3.9 1391 PID2 Set Point 2 Boost 2,3 RW
Use this parameter to set the value the set point can be boosted when going into sleep mode.
This is an additive variable that will add to the setpoint before drive output goes to sleep to prevent
premature cycling.
P8.3.3.10 1416 PID2 Set Point 2 Comp Enable 2,3 RW
Use this parameter to enables pressure loss compensation for set point 2 signal value. This is
used in pump systems to compensate the pressure loss that occurs at the end of the pipe line due to
the liquid flow.