Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P12.4.2.7 68 Trusted IP White List 1,2,3 RW
With P12.4.2.6, only IP addresses located in the white list can be used with the drive (cybersecurity).
P12.4.3.1 1733 BACnet IP UDP port number 1,2,3 RW
The UDP port for the BACnet IP communication.
P12.4.3.2 1734 BACnet IP Foreign Device 1,2,3 RW
The foreign device feature is used when the device is located in a different network than the BBMD. A
normal router does not send broadcast messages between different networks. The ‘Foreign device’ feature
solves this problem by establishing a connection to the BBMD with unicast messages. All broadcast
messages are forwarded to a BBMD device that takes care of receiving and transmitting broadcast messages
in both directions for all foreign devices.
P12.4.3.3 1735 BACnet IP BBMD IP 1,2,3 RW
The IP address of the BACnet IP Broadcast Management Device.
P12.4.3.4 1737 BACnet IP BBMD Port 1,2,3 RW
The BBMD Port number.
P12.4.3.5 1738 BACnet IP Registration Interval 1,2,3 RW
The registration interval to keep a live connection to the BBMD. Unit is seconds.
P12.4.3.6 1739 BACnet IP Comm Timeout 1,2,3 RW
Defines the number of seconds after a timeout is indicated after a communication break or disconnected
EtherNet link. Value 0 disables communication link supervision.
P12.4.3.7 1740 BACnet IP Protocol Status 1,2,3 RO
Fieldbus Protocol Status tells the status of the protocol.
P12.4.3.8 1741 BACnet IP Fault Behavior 1,2,3 RW
Defines when Fieldbus fault to be raise if fault condition is detected.
P12.4.3.9 1742 BACnetIP Instance Number 1,2,3 RW
The Device Object’s Instance number is used in conjunction with the MAC address to assign the devices
on the network. The instance number can have up to 127 nodes on it before a different instance number is
required.
P13.1.1 340 Language 1,2,3 RW
Use this parameter to allow to control the frequency converter through the keypad in the language of your
choice.
P13.1.2 142 Application 1,2,3 RW
Use this parameter to set the active application marco to use.
P13.1.3 619 Parameter Sets 1,2,3 RW
Use this parameter to reload the factory default parameter values, and to store and load two customized
parameter sets.
0 = No
1 = Reload Default
2 = Reload Set #1
3 = Reload Set #2;
4 = Store Set #1;
5 = Store Set #2;
6 = Reset;
7 = Reload Defaults VM
P13.1.4 620 Up To Keypad 1,2,3 RW
Use this parameter to enable uploading all parameter to the keypad.
0 = No
1 = Yes (All parameters)
P13.1.5 621 Down From Keypad 1,2,3 RW
Use this parameter to enable downloading parameter from the keypad.
0 = No
1 = All parameters
2 = All Parameter, No Motor
3 = App Parameter