18 Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
Up to 5000 feet above sea level without de-rating.
Above 5000 feet, output current is de-rated by 6% per 1000 feet.
Relative humidity: 0 to 95% without condensation
Audible Noise: 65 dBA at 5 ft. without alarm activation
33..55 SSyysstteemm EElleeccttrriiccaall SSppeecciiffiiccaattiioonn
Voltage:
Nominal STS input voltage ratings are 600VAC, 480VAC, 400VAC, 240VAC, 208VAC, LL RMS 3- phase, (3)
wires + ground.
Voltage Range: +/-10% of nominal
Source Voltage Distortion: Up to 15% THD plus notches, flat topping, and/or ringing transients
The STS output voltage is the same as the input voltage.
Frequency: (60) Hz. +/-0.5 Hz; (50) Hz +/-0.5Hz
Current:
The STS continuous current rating is 2000A input and output.
If the STS output is to a PDU, the STS continuous current rating must match or exceed the PDU input
rating.
Short circuit rating: 65 KAIC up to 600 volts
Load Power Factor Range: 0.5 to 1.0, leading or lagging
Load Crest Factor: Up to 3.5
Overload Capacity with Molded Case Circuit Breaker (MCCB) trip settings set to highest limits:
125% for 15 minutes
150% for 2 minutes
300% for 30 seconds
500% for 10 seconds
Ground: STS2000A system includes a computer grade single-point ground compliant with FIPS Pub 94 and
NEC requirements.
33..66 SSuurrggee PPrrootteeccttiioonn
The STS will safely withstand without mis-operation or damage:
Transient voltage surges on either AC power input as defined by ANSI/IEEE C62.41 for Category B3
locations (high surge exposure industrial and commercial facilities)
Electrostatic discharges (ESD) up to 10 kV at any point on the exterior of the unit
Electromagnetic fields from portable transmitters within 3 feet (1 meter) of the unit
Grounding for the WaveStar Static Transfer Switch must comply with local building codes and National Electric
Codes.