Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01 83
CChhaapptteerr 1166 DDiiggiittaall aanndd AAnnaalloogg PPooiinnttss
1166..11 DDiiggiittaall SSccrreeeenn PPooiinnttss
Table 6 shows the digital points as they show on the screen for the Digital Points List (Rev 2.86 and higher).
The Normal and Abnormal columns show what is Normal for the digital point (and hence not an alarm) and what
is Abnormal (hence an alarm). These columns are meaningful only for points that are Alarms (as noted in the
Alarm column).
Example: "Retransfer" (point 8) is not an alarm ("No" in Alarm column).
The same point name is used when the point appears on the Digital Values Screen, the Event Log Screen, or
the Alarms Screen. The status for digital points is in an adjacent table following the list of points.
Custom STSs will have different points and the current points list may not apply.
Table 6. Digital Screen Points
Name Normal Abnormal Alarm Alarm
Index
Status Status Index Normal
Value
Isolation 1 MCSW Closed Open Yes
1
Yes 1001 1
Isolation 2 MCSW Closed Open If Installed 2 Yes 1002 1
Bypass 1 MCSW Open Closed Yes 3 Yes 1003 0
Bypass 2 MCSW Open Closed Yes
4
Yes
1004 0
Input 1 MCSW Closed Open Yes
5
Yes
1005 1
Input 2 MCSW Closed Open
Yes 6 Yes 1006 1
Override
No Yes No
7 1007 0
Retransfer Yes No No 8 Yes 1008 1
ROI in Control No Yes Yes 9 Yes 1009 0
Preferred Source
1 2 No 10 Yes 1010 0
PDU 1 CB Closed Open If Installed
11
If Installed 1011 1
PDU 2 CB Closed Open If Installed 12 If Installed 1012 1
Building 1 OK Alarm If Installed
13
If Installed
1013 0
Building 2 OK Alarm If Installed
14
If Installed
1014 0
Building 3
OK
Alarm If Installed
15
If Installed
1015 0
Building 4 OK Alarm If Installed
16
If Installed
1016 0
Building 5 OK Alarm If Installed
17
If Installed
1017 0
Building 6
OK
Alarm If Installed
18
If Installed
1018 0
Building 7 OK Alarm If Installed
19
If Installed
1019 0
Building 8 OK Alarm If Installed
20
If Installed
1020 0