84 Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
Table 6. Digital Screen Points (Continued)
Name Normal Abnormal Alarm Alarm
Index
Status Status Index Normal
Value
Output Short OK Alarm Yes
21
No
1021 0
Open S1 OK Alarm Yes
22
No
1022 0
Open S2 OK
Alarm Yes 23 No 1023 0
EPO OK
Alarm Yes 24 No 1024 0
Remote EPO OK Alarm If Installed
25 No 1025 0
XFMR 1 HT OK Alarm If Installed
26
If Installed
1026 0
XFMR 1 OT OK Alarm If Installed
27
If Installed
1027 0
XFMR 2 HT OK Alarm If Installed
28
If Installed
1028 0
XFMR 2 OT OK Alarm If Installed
29
If Installed
1029 0
SCR High Temp OK Alarm Yes 30 No 1030 0
SCR Over Temp OK
Alarm Yes 31 No 1031 0
Shunt Trip 1 OK Trip No 32 No 1032 0
Shunt Trip 2 OK Trip No 33 No 1033 0
DCPS S1V OK Alarm Yes 34 No 1034 0
DCPS S2V OK Alarm Yes 35 No 1035 0
DCPS OV OK Alarm Yes 36 No 1036 0
S1 Rotation OK Alarm Yes 37 No 1037 0
S2 Rotation OK Alarm Yes 38 No 1038 0
On Source Preferred Alt Yes
39
No
1039 0
Transfer None Done No
40
No
1040 0
Shunt Trip OK Fail No
41
No 1041 0
EPO Latched OK Alarm No 42 No 1042 0
SAS D Open OK Alarm Yes 43 No 1043 0
SAS D DC OK Alarm Yes
44
No 1044 0
SAS D DC 1 OK Alarm Yes
45
No 1045 0
SAS D DC 2 OK Alarm Yes 46 No 1046 0
SAS D DC Main OK Alarm Yes
47
No 1047 0
SAS D Pulse 1 OK Alarm Yes
48
No
1048 0
SAS D Pulse 2 OK Alarm Yes
49
No
1049 0
SAS D Pulse M OK
Alarm Yes 50 No 1050 0
SAS D Voting OK
Alarm Yes
51
No 1051 0