Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01 85
Table 6. Digital Screen Points (Continued)
Name Normal Abnormal Alarm Alarm
Index
Status Status Index Normal
Value
SAS D SCR 1 DC Off On No
52
No
1052 0
SAS D SCR 2 DC Off On No
53
No
1053 0
SAS D Aux 3 OK
Alarm Yes
54
No 1054 0
SAS D Aux 4 OK
Alarm Yes
55
No 1055 0
SAS D Aux 5 OK Alarm Yes 56 No 1056 0
SAS D Aux 6 OK Alarm Yes
57
No 1057 0
SAS D Aux 7 OK Alarm Yes 58 No 1058 0
SAS 1 Fiber Rx OK Failed Yes 59 No 1059 0
SAS 2 Fiber Rx OK Failed Yes 60 No 1060 0
SAS 3 Fiber Rx OK Failed Yes 61 No 1061 0
SAS 1 In Control No Yes Yes 62 No 1062 0
SAS 2 In Control No Yes Yes
63
No
1063 0
SAS 3 In Control No Yes Yes
64
No
1064 0
SAS In Control
No Yes Yes 65 No 1065 0
SAS 1 SCR 1 OK Short
Yes 66 No 1066 0
SAS 2 SCR 1 OK Short
Yes 67 No 1067 0
SAS 3 SCR 1 OK Short Yes 68 No 1068 0
SAS 1 SCR 2 OK Short Yes 69 No 1069 0
SAS 2 SCR 2 OK Short Yes 70 No 1070 0
SAS 3 SCR 2 OK Short Yes
71
No 1071 0
SAS SCR 1 OK Short Yes 72 No 1072 0
SAS SCR 2 OK Short Yes 73 No 1073 0
SAS 1 S1 Gated Off On No
74
No 1074 0
SAS 2 S1 Gated Off On No
75
No
1075 0
SAS 3 S1 Gated Off On No
76
No
1076 0
SAS 1 S2 Gated Off On
No
77
No 1077 0
SAS 2 S2 Gated Off On
No 78 No 1078 0
SAS 3 S2 Gated Off On
No 79 No 1079 0
SAS S1 Gated Off On No 80 Yes 1080 0
SAS S2 Gated Off On No 81 Yes 1081 0
SAS D Timeout OK Alarm Yes 82 No 1082 0
SAS 1 Timeout OK Alarm Yes 83 No 1083 0
Digital and Analog Points