86 Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
Table 6. Digital Screen Points (Continued)
Name Normal Abnormal Alarm Alarm
Index
Status Status Index Normal
Value
SAS 2 Timeout OK Alarm Yes
84
No
1084 0
SAS 3 Timeout OK Alarm Yes
85
No
1085 0
ROI Timeout OK
Alarm Yes 86 No 1086 0
DCPS Timeout OK
Alarm Yes 87 No 1087 0
SAS Tx 1 Down OK Alarm Yes 88 No 1088 0
SAS Tx 2 Down OK Alarm Yes 89 No 1089 0
SAS Tx 3 Down OK Alarm Yes 90 No 1090 0
SAS Down OK Alarm Yes 91 No 1091 0
SAS 1 Fuse A OK Alarm Yes 92 No 1092 0
SAS 1 Fuse B OK Alarm Yes 93 No 1093 0
SAS 1 Fuse C OK Alarm Yes 94 No 1094 0
SAS 1 Output OK Failed Yes
95
No
1095 0
SAS 1 ROI OK In Control Yes
96
No
1096 0
SAS 1 Aux 5 OK
Alarm No 97 No 1097 0
SAS 1 Aux 6 OK
Alarm No 98 No 1098 0
SAS 1 Aux 7 OK
Alarm No 99 No 1099 0
SAS 2 Fuse A OK Alarm Yes 100 No 1100 0
SAS 2 Fuse B OK Alarm Yes 101 No 1101 0
SAS 2 Fuse C OK Alarm Yes 102 No 1102 0
SAS 2 Output OK Failed Yes 103 No 1103 0
SAS 2 ROI OK In Control Yes 104 No 1104 0
SAS 2 Aux 5 OK Alarm No 105 No 1105 0
SAS 2 Aux 6 OK Alarm No
106
No
1106 0
SAS 2 Aux 7 OK Alarm No
107
No
1107 0
SAS 3 Fuse A OK Alarm Yes
108
No
1108 0
SAS 3 Fuse B OK
Alarm Yes 109 No 1109 0
SAS 3 Fuse C OK
Alarm Yes 110 No 1110 0
SAS 3 Output OK Failed Yes
111
No
1111 0
SAS 3 ROI OK In Control Yes 112 No 1112 0
SAS 3 Aux 5 OK Alarm No 113 No 1113 0
SAS 3 Aux 6 OK Alarm No
114
No
1114 0
Digital and Analog Points