Loading...
Appendix
A.1 Technical data
Applies only to XV300 units with a XV-3.3-..-.E.-...-.. SmartWire-DT connection.
Supply voltage U
Aux
Rated operating voltage
24 V DC
Effective: 20.4-28.8 V DC (rated operating voltage -15/+20%)
Residual ripple of input voltage
max. 5%
Protection against polarity reversal
Yes
max. current
max. 3A
Notes
If contactors with a total current consumption > 3 A (for accept-
ance by UL: 2 A)are connected, a power feeder module EU5C-
SWD-PF1 or EU5C-SWD-PF2 has to be used.
Short-circuit rating
No, external protection using FAZ Z3 is required
Potential isolation
No
Heat dissipation
Normally 1.0 W
Rated operating voltage of 24-V-
DC
mod-
ules
Normally U
Aux
- 0.2 V
SmartWire-DT supply voltage U
Pow
Specifications for connection to supply
voltage
24 V DC
Effective: 20.4-28.8 V DC (rated operating voltage -15/+20%)
Residual ripple of input voltage
max. 5%
Protection against polarity reversal
Yes
rated operational current
max. 0.7 A
Overload proof
Yes
Inrush current and length
12.5 A/6 ms
Heat dissipation at 24 V DC
1.0 W
Bridging voltage dips
10 ms
Repetition rate
1s
Status indication
LED
SmartWire-DT interface
Potential isolation between U
Pow
and 15 V
SmartWire-DT supply voltage
No
Rated operating voltage Ue
14.5 V ± 3 % (14.0 ...15.0 V
DC
)
max. current
0.7 A
Notes
If SWD modules with a total power consumption > 0.7 A are
connected, a power feeder module EU5C-SWD-PF2 has to be
used.
Short-circuit rating
Yes
Module type
SWD master, coordinator
Number of SWD stations
Max. 99
Baud Rate
125 kBd | 250 kBd
Address setting
Automatic
Status indication
SWD master LED: green | Configurations LED: red
porting
Plug, 8-pole
Plug connectors
Blade terminal SWD4-8MF2
XV30004/19 MN048017ENwww.eaton.eu