Appendix
A.1 Technical data
Applied Standards and Policies List
Mechanical
shock res-
istance
IEC/EN 60068-2-27
15g /11ms
Vibration
IEC/EN 60068-2-6
Displacement amplitude: 5–9 Hz: 3.5 mm; 9–60 Hz: 0.15
mm
Acceleration amplitude: 60–150 Hz: 2 g
Free fall, pack-
aged
IEC/EN 60068-2-31
RoHS
Directive 2011/65/EG
conform
Climatic proof-
ing
Cold to IEC 60068-2-1
Damp heat as per EN 60068-2-3
Dry heat to IEC60068-2-2
Standard Overcurrent and short-circuit protective device
DIN VDE 0641, part 11 and
EC/EN 60898
Miniature circuit-breaker 24 V DC, rated operational current 3 A,
trip type Z fuse 3 A,
Utilization category gL/gG
UL 61010-2-201
Miniature circuit-breaker 24 V DC, rated operational current 2 A,
trip type Z fuse 2 A
Table 39: Overcurrent and short-circuit protective device standards
Ambient climatic conditions
Air pressure (in operation)
795 - 1080 hPa
max. 2000 m a. NHN (standard elevation zero)
Temperature
Operation
± 0 – +50 °C (+32 – +122 °F)
Mounting position
XV-303-10-…, XV-303-70-...
α ≦ ± 45°, T ≦ 50 °C (122 °F)
XV-303-15-.E.-..., XV-303-15-.02-..
α ≦ ± 10°, T ≦ 50 °C (122 °F)
XV-303-15-.00-...
α ≦ ± 10°, T ≦ 50 °C (122 °F)
α ≦ ± 45°, T ≦ 45 °C (113 °F)
Inclination from vertical: α ≦ ± 45° at operating temperature ≦ 45°C
possible (if using natural convection)
Storage / Transport
-20 – + 60 °C (-4 – +140 °F)
Relative humidity
Relative humidity 10 - 95 %
Condensation
non-condensing
XV30004/19 MN048017ENwww.eaton.eu
103