3. Installation
3.1 Prerequisites for the Area of application
3.1.3 Conditions for Marine approvals
The following DNV GL rules for shipping classification in accordance with DNVGL-CG-
0339 type approvals must be observed:
1. Complete and proper installation and commissioning in accordance with DNV GL
rules and Eaton requirements and specifications.
2. Installation of radio interference suppression filters for the 24 V DC supply.
3.1.3.1 Radio interference suppression filter for the 24 V DC supply
Additional interference filters must be installed for the power supply in order to adhere
to the EMC B provisions.
Integrate a radio interference suppression filter into the wiring.
Depending on the output, the following filters can be used:
• XT-FIL-1 suppression filter for 24-V-DC supply up to 2.2 A (Eaton article no. 285316)
Or
• XT-FIL-2 suppression filter for 24-V-DC supply up to 12 A (Eaton article no. 118980)
Figure 17: Engineering example for integration of radio interference suppression filters
Earthing is ensured either by using
l the filter's integrated contact fields onto a grounded metal plate
or using
40