EasyManua.ls Logo

Eaton XV300 - Power Supply Electrical Connection

Eaton XV300
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Installation
3.4 Preparing the device for operation
3.4.2 Power supply - electrical connection
signal Configuration
0 V+24 V DC n.c.
+
Supply voltage
+ 24 VDC SELV (safety extra low voltage)/PELV (protective extra low
voltage)
n.c.
not used
Supply voltage 0 V
Table 12: Configuration Plug connector MSTB 2.5/3-ST-5.08
Specifications for connection to 24 VDC supply voltage
Copper conductor
60° / 70°C
Cross section
min. 0.75 mm
2
/ max. 2.5 mm
2
(drain wire or conductor)
min. AWG18 / max. AWG12
tightening torque
0.6 ... 0.8 Nm (5 ... 7 lb-in)
for the screws on the Plug connector MSTB 2.5/3-ST-5.08
Strip length
7 mm
Table 13: Specifications for connection to 24 VDC supply voltage
Power supply
+24 V DC
0 V
U
e
= 24 V DC
(19.2 - 30 V DC SELV)
I
e
= ...
0 V
+24 V DC
0.6 - 0.8 Nm
(5 - 7 lb-in)
Figure 26: Connecting the screw terminals on the Plug connector MSTB 2.5/3-ST-5.08
Electrical connection
0 V+24 V DC
Figure 27: Power supplied through Plug connector MSTB 2.5/3-ST-5.08
52
XV30004/19 MN048017ENwww.eaton.eu

Table of Contents