3. Installation
3.1 Prerequisites for the Area of application
The environmental ambient conditions for operation must not exceed the specified val-
ues:
Ambient climatic conditions
Air pressure (in operation)
795 - 1080 hPa
max. 2000 m a. NHN (standard elevation zero)
Temperature
Operation
± 0 +50 °C (+32 – +122 °F)
Mounting position
αα
XV-303-10-…, XV-303-70-...
α ± 45°, T 50 °C (122 °F)
XV-303-15-.E.-..., XV-303-15-.02-..
α ± 10°, T 50 °C (122 °F)
XV-303-15-.00-...
α ± 10°, T 50 °C (122 °F)
α ± 45°, T 45 °C (113 °F)
Inclination from vertical: α ≦ ± 45° at operating temperature ≦ 45°C
possible (if using natural convection)
Storage / Transport
-20 + 60 °C (-4 +140 °F)
Relative humidity
Relative humidity 10 - 95 %
Condensation
non-condensing
3.1.1.2 Aeration and de-aeration
l Do not block the ventilation openings when mounting the device:
They are designed to allow air to circulate in order to cool the HMI panel.
l The device uses natural convection-based passive cooling, i.e., it does not use fans.
36