5. External connections
5.8 XV300 multi touch display as SmartWire-DT coordinator
Load the PLC project onto the XV300 multi touch display.
Configuration check
The configurations are compared every time the power supply is switched on.
l The modules that are actually on the network will be compared with the target con-
figuration stored on the device:
If the SmartWire-DT network's physical configuration matches the target con-
figuration, the SmartWire-DT network will be ready to start transferring data.
l The target configuration stored in the device will be compared with the project con-
figuration defined in the PLC:
If the target configuration matches the project configuration, the Config LED will light
up with a solid green light.
SWD-LED
Indicates whether the physical configuration of the SWD network matches the target con-
figuration stored in the XV300.
status
Description
off
No target configuration present
Red continuous light
• Short-circuit on the 15V DC power supply.
• No SmartWire-DT module found.
Red flashing
The modules found in the SmartWire-DT network do
not match the target configuration.
A SmartWire-DT module configured as necessary is
missing.
Flashing with an orange light
The SmartWire-DT network's physical configuration is
being imported and stored as a new target con-
figuration in the device.
GREEN flashing
• The physical configuration of the SmartWire-DT net-
work is compared with the target configuration.
• The SmartWire-DT modules are addressed.
Green continuous light
• The modules found in the SmartWire-DT network
match the target configuration.
• The SmartWire-DT network is ready for data
exchange.
Table 26: SWD-LED
Config-LED
Indicates whether the SWD master project configuration defined in the PLC
matches the SWD network target configuration stored in the XV300.
status
Description
off
• No project configuration present.
• Incorrect target configuration (see LED
SWD).
Table 27: Config-LED
72
XV30004/19 MN048017ENwww.eaton.eu