5. External connections
5.8 XV300 multi touch display as SmartWire-DT coordinator
Load the PLC project onto the XV300 multi touch display.
Configuration check
The configurations are compared every time the power supply is switched on.
l The modules that are actually on the network will be compared with the target con-
figuration stored on the device:
If the SmartWire-DT network's physical configuration matches the target con-
figuration, the SmartWire-DT network will be ready to start transferring data.
l The target configuration stored in the device will be compared with the project con-
figuration defined in the PLC:
If the target configuration matches the project configuration, the Config LED will light
up with a solid green light.
SWD-LED
Indicates whether the physical configuration of the SWD network matches the target con-
figuration stored in the XV300.
status
Description
off
No target configuration present
Red continuous light
Short-circuit on the 15V DC power supply.
No SmartWire-DT module found.
Red flashing
The modules found in the SmartWire-DT network do
not match the target configuration.
A SmartWire-DT module configured as necessary is
missing.
Flashing with an orange light
The SmartWire-DT network's physical configuration is
being imported and stored as a new target con-
figuration in the device.
GREEN flashing
The physical configuration of the SmartWire-DT net-
work is compared with the target configuration.
The SmartWire-DT modules are addressed.
Green continuous light
The modules found in the SmartWire-DT network
match the target configuration.
The SmartWire-DT network is ready for data
exchange.
Table 26: SWD-LED
Config-LED
Indicates whether the SWD master project configuration defined in the PLC
matches the SWD network target configuration stored in the XV300.
status
Description
off
No project configuration present.
Incorrect target configuration (see LED
SWD).
Table 27: Config-LED