Menu structure UA 300 D Controller type UR 141
85
E 2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S Screen 2−1−4 Zone 2A Altern.
Shown only when two−zone operation is set (Screen 6−1) and setpoint toggle is not disabled (Screen 3−3).
COOLING 2A POS: XXXXX Entry Default
Setpoint R4.3 XXX °C Room air sensor setpoint −10..30 0 °C
Hystersis R4.3 X K Room air sensor hysteresis setpoint 1..8 2 K
S Screen 2−2 Defrost
DEFROST POS: XXXXX
1 Zone 1 Continue to Screen 2−2−1
2 Zone 2 Continue to Screen 2−2−2; shown only when two−zone operation is set (Screen 6−1)
3 Zone 1A Altern. Continue to Screen 2−2−3; shown only when setpoint toggle is enabled (Screen 3−3)
4 Zone 2A Altern. Continue to Screen 2−2−4; shown only when two−zone operation is set (Screen 6−1) and only
when setpoint toggle is enabled (Screen 3−3)
S Screen 2−2−1 Zone 1
DEFROST 1 POS: XXXXX Entry Default
Counting Rate X Counting rate setpoint 0..15 0
Defrost Counter X Defrost counter −
Def. End. Tmp. XX °C Defrost termination temperature setpoint −−, −10..30 12 °C
Wait Time Xm Waiting time setpoint 0..15 0m
Drip Time Xm Drip time setpoint 0..15 3m
S Screen 2−2−2 Zone 2
DEFROST 2 POS: XXXXX Entry Default
Counting Rate X Counting rate setpoint 0..15 0
Defrost Counter X Defrost counter −
Def. End. Tmp. XX °C Defrost termination temperature setpoint −−, −10..30 12 °C
Wait Time Xm Waiting time setpoint 0..15 0m
Drip Time Xm Drip time setpoint 0..15 0m