Menu structure UA 300 D Controller type UR 141
86
Version 2.03 27. Juni 2008
S Screen 2−2−3 Zone 1A Altern.
DEFROST 1A POS: XXXXX Entry Default
Counting Rate X Counting rate setpoint 0..15 0
Defrost Counter X Defrost counter
Def. End. Tmp. XX °C Defrost termination temperature setpoint −−, −10..30 12 °C
Wait Time Xm Waiting time setpoint 0..15 0m
Drip Time Xm Drip time setpoint 0..15 3m
S Screen 2−2−4 Zone 2A Altern.
DEFROST 2A POS: XXXXX Entry Default
Counting Rate X Counting rate setpoint 0..15 0
Defrost Counter X Defrost counter
Def. End. Tmp. XX °C Defrost termination temperature setpoint −−, −10..30 12 °C
Wait Time Xm Waiting time setpoint 0..15 0m
Drip Time Xm Drip time setpoint 0..15 0m
S Screen 2−3 Fans
FANS POS: XXXXX
1 Zone 1 Continue to Screen 2−3−1
2 Zone 2 Continue to Screen 2−3−2; shown only when two−zone operation is set (Screen 6−1)
3 Zone 1A Altern. Continue to Screen 2−3−3; shown only when setpoint toggle is enabled (Screen 3−3)
4 Zone 2A Altern. Continue to Screen 2−3−4; shown only when two−zone operation is set (Screen 6−1) and only
when setpoint toggle is enabled (Screen 3−3)
S Screen 2−3−1 Zone 1
FANS 1 POS: XXXXX Entry Default
Fan Delay XX °C Temperature at which fan starts with delay −−, −20..20 −3 °C
Start Delay XX m Cooling start delay 0..60 15m
S Screen 2−3−2 Zone 2
FANS 2 POS: XXXXX Entry Default
Fan Delay XX °C Temperature at which fan stops with delay −−, −20..20 2 °C
Overrun Time XX m Fan stop delay 0..60 15m