EasyManua.ls Logo

ECKELMANN VS 3000 - S Menu 3-2-1-3 LP-Control day; S Masque 3-2-1-3-a Basic load time

Default Icon
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version 2.02 15.05.2007
Menu Structure of VS 3000
97
eckelmann.de
E 2007 - ECKELMANN AG | BERLINER STRASSE 161 | 65205 WIESBADEN | TELEFON + 49(0)611 71 03-0 | FAX +49(0)611 71 03-133
S Menu 3-2-1-3 LP-Control day
LP CONT D POS: XXXXX Entry
Default / Dimension
NT LT Dim.
to-max. XXX °C Max. t
0
setpoint for setpoint shift -50..10 -8 -34 °C
tr-min. XXX °C min room temperature for setpoint shift
(Only shown when t0 shift by room temperature is
selected in Screen 3-2-2-a)
-25..20 15 15 °C
to-min. XXX °C min t
0
setpoint for setpoint shift -50..1 0 -12 -38 °C
tr-max. XXX °C Max. room temperature for setpoint shift
(Only shown when t0 shift by room temperature is
selected in Screen 3-2-2-a)
-18..35 25 25 °C
humid. adapt. X Humidity shift activated Y/N , ,(Y/N) N N -
Basic load time ON Show basic times t
b
ON Screen 3-2-1-3-a
Vari. load time ON Show variable times t
v
ON Screen 3-2-1-3-b
Basic unload time OFF Show basic times t
b
OFF Screen 3-2-1-3-c
Vari. unload time OFF Show variable times t
v
OFF Screen 3-2-1-3-d
Dead band XX K Switching hysteresis 1..10 4 4 K
Control const. XX K Max. control error for variable control times 1..15 10 7 K
S Masque 3-2-1-3-a Basic load time
B. LOAD T POS: XXXXX Entry
Default / Dimension
NT LT Dim.
BasLoadTC1 XXXs 0..250 30 60 sec
BasLoadTC2 XXXs 3..250 60 140 sec
BasLoadTC3 XXXs
O
n
l
y
t
h
e
a
v
a
i
l
a
b
l
e
c
a
p
a
c
i
t
y
s
t
a
g
e
s
a
r
e
s
h
o
w
n
3..250 90 200 sec
BasLoadTC4 XXXs
Onl
y
the available capacit
y
stages are shown
3..250 120 250 sec
BasLoadTC5 XXXs 3..250 150 250 sec
BasLoadTC6 XXXs 3..250 180 250 sec
...
O
n
l
y
t
h
e
a
v
a
i
l
a
b
l
e
c
a
p
a
c
i
t
y
s
t
a
g
e
s
a
r
e
s
h
o
w
n
BasLoadTC12 XXXs
Onl
y
the available capacit
y
stages are shown
3..250 180 250 sec
VS 3000 basic module: Capacity stage 1 - max. 4
With 1st SIOX extension module: Capacity stage 1 - max. 8
With 2nd SIOX extension module: Capacity stage 1 - max. 12