Version 2.02 15.05.2007
Menu Structure of VS 3000
89
eckelmann.de
E 2007 - ECKELMANN AG | BERLINER STRASSE 161 | 65205 WIESBADEN | TELEFON + 49(0)611 71 03-0 | FAX +49(0)611 71 03-133
S Menu 2-1 Analog values
ANALOG VAL POS: XXXXX Display refrigeration point data archived in Store Computer Entry
Act. ND +/-/= X.XX b Current evaporating pressure
Setp. ND T/N X.XX b Evaporating pressure setpoint for comparison
Act. to +/-/= XX °C Current evaporating temperature
Setp. to T/N XX °C Evaporating temperature setpoint for comparison
Suct.gas temp XX °C Current suction gas temperature
Superheat. XX °C Current suction gas superheat
Room temp. XX °C Current room temperature (optional)
Act. HD -/+/= X.XX b Current condensing pressure
Setp. HD WRG X.XX b Condensing pressure setpoint for comparison
Act. tc -/+/= XX °C Current condensing temperature
Setp. tc WRG XX °C Condensing temperature setpoint for comparison
Outdoor temp. XX °C Current outdoor temperature (optional)
Humidity XXX% Current humidity of air
Cyl.temp. → Analog values cylinder head temperatures.
Move to Screen 2-1-a
→
Analogausg.FU XXX% Frequency or current input of FC can be delivered through a programmable
output of the FC. This output can be read with analog current/voltage input
2 (terminals 38-40) and displayed
(Only shown when LP control type configured as combined controller in
Screen 3-2-1-a)
Soll FU XXX% Shows FC setpoint with compressor combined control
(Only shown when LP control type configured as combined controller in
Screen 3-2-1-a)
S Menu 2-1-a Analog Values Cylinder Head Temperatures
ANALOG VAL. POS: XXXXX
Zyl. Temp. V1 XX °C Cylinder head temperature Compressor 1
... Only the actual number of compressors is shown.
Zyl. Temp. V12 XX °C Cylinder head temperature Compressor 12
VS 3000 basic module: Cylinder head temperature Compressor 1 - max. 4
With 1st SIOX extension module: Cylinder head temperature Compressor 1 - max. 8
With 2nd SIOX extension module: Cylinder head temperature Compressor 1 - max. 12