EasyManua.ls Logo

Econ sens3 - Page 44

Econ sens3
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation and parameterization 40
Manual econ sens3 Version 3.0
It can be seen in the measurement value table that the power factor of phase 2 has fallen below 0.71
and the phase displacement between U2 and I2 in the “phase angle” graphic shows 125.3°. This is a
typical error pattern for the installation error mentioned above. The “Phase check” function provides an
indication of this (see Figure 36).
Note:
Because of the simplicity of the installation test routine, there are cases in which no installation error
occurred but the routine nevertheless outputs an error message, e.g.:
a. ) In the measured network, only generated and little to no consumed power occurs
b. ) The power factor of the connected load is in fact < 0.71
Warning appears under the Phase check buttons.
Figure 35: Error message
Figure 36: Phase check

Table of Contents

Other manuals for Econ sens3