EasyManua.ls Logo

elco TRIGON L PLUS - Component Checks and Replacements

elco TRIGON L PLUS
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
Maintenance
Maintenance details
The ignition electrode
The ignition electrode (1) is a
consumablepartandmustbechecked
Checking the air pressure
di󰀨erential switch + side
- Switcho󰀨theboiler
- Disconnect the silicon hose on
the + side (P1) of the air pressure
di󰀨erentialswitch(1).
annually.Theelectrodemustbe
renewed, if damages or any wear and
tear is detected. The value of ignition
electroderesistancecanbedetected
through measurements.
The maximum electrode resistance at
room temperature should not exceed
100Ω.
Itcanbereplacedunscrewingitfrom
the heat exchanger. Remove and
replace the o-ring. Make sure of the
tightness of the connection.
In case electrode damage is detected,
verify the status and eventually replace
thefusealongelectrodecable.
In order to ensure continued good
andsafeoperationoftheboiler
ignitionelectrodeshouldbereplaced
every 2 years.
The detection electrode.
The detection electrode (2) is a
consumablepartandmustbechecked
annually.Theelectrodemustbe
renewed, if damages or any wear and
tearisdetected,butcertainlyevery4
years. Furthermore, the value of the
ionizationcurrentcanbedetected
through measurements. Under full load
operations, the minimum ionization
currentmustamountto4μA.
Itcanbereplacedunscrewingitfrom
the heat exchanger. Remove and
replace the o-ring. Make sure of the
tightness of the connection.
Sight glass
If the sight glass (3) is damaged, it can
bereplacedunscrewingitfromthe
heat exchanger. Remove and replace
the gasket. Make sure the gasket is in
correct position and the connection of
new glass is tight.
Assemblyisdoneinreverseorder.
2
1
3
P
1
(
+
) P
2
(-)
(
+
)
1
3
2
4
5
6
- Take a large plastic syringe
orbellowsandconnectaTpiece
with a hose connected (2).
- Connect the + side of the air-
pressuredi󰀨erentialswitchtoone
end of the T piece with a hose (3).
- On the other end of the T piece,
connect the + side of a pressure
gauge (4).
- Turnontheboiler.
- Pushthesyringeorbellowsinvery
slowlyuntiltheboilergoesinto
failure mode (5).
- Make a note of the pressure
indicatedbythepressuregauge
at that point. A switch pressure of
between5.0and6.5mbarisne.
A lower or higher switch pressure
indicatesaproblemwiththeair
pressuredi󰀨erentialswitch.
- After taking a measurement, detach
the silicon hose from the T piece on
the + side and reconnect the hose
that was previously removed.
CAUTION:
Please note: The + side (P1) is the rear
connector nipple of the air pressure
di󰀨erential switch (without red cap).
- Remove any soiling from all
connection points for hoses and the
airpressuredi󰀨erentialswitch.
- Check the condition and tightness
of the hoses of the air pressure
di󰀨erentialswitch.Replacethe
hoses if necessary.

Table of Contents

Related product manuals