EasyManua.ls Logo

Elvaco CMeX50 - Slave to Master; Set Language; Master to Slave

Elvaco CMeX50
89 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CMeX50 Users Manual English
CMeX50 Users Manual English
3
0x68
Start character 2
4
0x43 | 0x53 | 0x63 | 0x73
C-Field = SND_UD
5
0xnn
A-Field = Address of slave
6
0x51
CI-Field = Master to slave data send
7-13(14)
0x017C0364636Cnn
OR
0x01FC0364636C00nn
Write LCD contrast
nn = 8 bit signed LCD contrast offset.
Valid range: -10 (brightest) .. +10 (darkest)
14(15)
0xnn
Checksum
15(16)
0x16
Stop character
6.3.23.2 Slave to master
Byte index
Data
Description
0
0xe5
Acknowledge
6.3.24 Set language
Set the LCD display language.
6.3.24.1 Master to slave
Byte index
Data
Description
0
0x68
Start character 1
1
0xnn
L-Field 1
2
0xnn
L-Field 2
3
0x68
Start character 2
4
0x43 | 0x53 | 0x63 | 0x73
C-Field = SND_UD
5
0xnn
A-Field = Address of slave
6
0x51
CI-Field = Master to slave data send
7-13(14)
0x017C036E616Cnn
OR
0x01FC036E616Cnn
Write language
nn = 8 bit unsigned language
Valid values:
0 = English
1 = Swedish
2 = German
14(15)
0xnn
Checksum
15(16)
0x16
Stop character
6.3.24.2 Slave to master
Byte index
Data
Description

Table of Contents