Figure A-4: Loop Resistance: Active IS Analog Input
%
$
$
$
A. Loop resistance [Ω]
B. Lift-off voltage [V]
Max Loop Resistance
(14)
= (20.1 – Lift-off Voltage)/Max Loop Current – 590 [Ω]
Analog output
Maximum number of output channels: 1
Output range: 3.5-23 mA
Software configurable High and Low Alarm Limits.
Separate software configurable alarms for process and hardware failures.
Low voltage and invalid loop current detection.
SIL 2 capable.
External Supply Voltage:
• Passive Non-IS: 8.0 - 35 Vdc
• Passive IS: 9.4 – 30 Vdc
Maximum Output Voltage (open loop):
• Active Non-IS: 24 Vdc
• Active IS: 23 Vdc
Reference Manual Specifications and reference data
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 117