Table 3-5: Minimum Cable Area for the TRL2 Bus
Maximum distance Minimum cross-sectional area
3 km 0.50 mm
2
(AWG 20)
4 km 0.75 mm
2
(AWG 18)
Note
Wherever two or more TRL2 buses run alongside each other, sharing the same cable or
conduit tube, use twisted and shielded wire and ensure that each pair of bus wires is
individually shielded in order to avoid crosstalk.
Figure 3-13: Individually Shielded Pair Cables Minimizes Crosstalk
Table 3-6 shows typical cable types that can be used for connecting the TRL2 bus. Other
cables of similar type may also be used.
Table 3-6: Recommended Cable Standards for the TRL2 Bus
Type Manufacturing standard Core size
Signal BS 5308 part 1, type 1 1 mm
2
Signal (armoured) BS 5308 part 2, type 1 1 mm
2
RS485 Bus
The RS485 bus should meet the following requirements:
twisted and shielded pair wiring
characteristic impedance of 120 Ω
maximum cable length 1200 m / 4000 ft.
Reference Manual Installation
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 49