7. Click the Start Programming button.
Now the Start Device Programming window appears.
8. Click the Start Programming button to activate device programming.
Programming may take up to two hours for a Rosemount 2410 connected to a
TankMaster PC via a 2460 System Hub. The programming procedure will continue
with one device after the other until all Tank Hubs selected in the Program Devices
window are upgraded. The Rosemount 2410 operates as normal during the
reprogramming procedure.
By connecting a Rosemount 2410 directly to a host computer, and using the RS485
Modbus
®
protocol at a maximum baud rate of 38400, programming time may be
reduced to 5 to 10 minutes (see Change the communication parameters for the
primary bus for information on how to configure the Primary Bus).
Once programming is finished, the tank hub will automatically perform a restart
indicated by "WAIT" on the integral display for a couple of minutes.
Postrequisites
Note
In case the current firmware version is significantly older than the new one, it is
recommended that you load the default configuration database once the device is
reprogrammed. Contact Emerson Automation Solutions/Rosemount Tank Gauging
service department if you need further advice.
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 87