6.2.9 Write protection switch
A switch on the front of the Rosemount 2410 Tank Hub can be used to prevent
unauthorized changes of the holding register database.
Figure 6-2: The Rosemount 2410 Tank Hub Write Protection Switch on the Built-in
Integral display
A. Write protection switch
6.2.10
Simulation mode
The Simulation Mode function lets you verify communication between a Rosemount 2410
Tank Hub and a host system without connecting actual field devices.
The Rosemount 2410 Tank Hub Simulation window allows you to choose which parameters
to be calculated by the Rosemount 2410. Calculations are based on input from simulated
tank measurement data such as product level, average temperature, liquid pressure, and
other variables.
The Simulation HREGS holding registers (starting with register number 3800) lets you
specify the desired simulation data.
For information on how to view and edit holding registers, see Viewing input and holding
registers using TankMaster
™
or the Rosemount Tank Gauging System Configuration
Manual (Document No. 00809-0300-5100).
Procedure
1. In the TankMaster WinSetup workspace select the Rosemount 2410 icon.
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 89