2. Click the right mouse button and choose the Simulation option to open the
Rosemount 2410 Tank Hub Simulation window:
3. Choose simulation mode Single Tank and the desired tank in the Tank Position
field, or choose the All option to simulate all tanks connected to the Rosemount
2410.
Tank Position refers to the position in the Rosemount 2410 tank database.
4. In the Simulation Time field, enter for how long the simulation will continue.
Simulation can be stopped at any time by pressing the Stop button.
5. Calculate Parameter.
In the standard configuration the check-boxes are unchecked, which means that
each simulation parameter is given a specific standard simulation value as specified
in the simulation holding register area:
Table 6-2: Simulation Paramters
Simulation Parameter Simulation Holding Register
Average Temperature HR3868
Total Observed Volume HR3994
Observed Density HR3976
Service and troubleshooting Reference Manual
December 2019 00809-0100-2410
90 Reference Manual