Figure 4-13: The HMC Module Supports up to Four External Devices (Slaves)
A. RS-485 bus
B. Power supply
C. Up to four external devices
D. External HART device 2
E. External HART device 1
4.8 FOUNDATION
Fieldbus
4.8.1 Power requirements
Terminals in the transmitter housing provide connections for signal cables. The
Rosemount 5300 Level Transmitter is powered over FOUNDATION
Fieldbus with standard
fieldbus power supplies. The transmitter operates with the following power supplies:
Table 4-5: External Power Supply for F
OUNDATION Fieldbus
Approval type Power supply (Vdc)
None 9 - 32
Non-sparking/Energy limited 9 - 32
Intrinsically Safe 9 - 30
FISCO 9 - 17.5
Explosion-proof/flameproof 16 - 32
Reference Manual Electrical installation
00809-0100-4530 April 2019
Reference Manual 105