Standards
CSA C22.2 No.0-M91, CSA C22.2 No.25-1966, CSA C22.2 No.30-M1986,
CSA C22.2 No.94-M91, CSA C22.2 No.142-M1987, CSA C22.2 157-92,
CAN/CSA C22.2 No. 60529:05, ANSI/ISA 12.27.01-2003
Markings
CL I, DIV 1, GP A, B, C, D, T4 see installation drawing 9240030-937; Non-
Incendive Class III, DIV 1, Haz-loc CL I DIV 2, GP A, B, C, D, Maximum
Ambient Temperature +60 °C, T4, Type 4X/IP66/IP67, Maximum Working
Pressure 5000 psi, Dual Seal.
Ui Ii Pi Ci Li
FISCO parameters 17.5 V 380 mA 5.32 W 0 0
B.7 Europe
B.7.1 E1 ATEX Flameproof
Certificate
Nemko 04ATEX1073X
Standards
EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN
60079-26:2015, EN 60079-31:2014
Markings
II 1/2G Ex db ia IIC T4 Ga/Gb, (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
II 1D Ex ta IIIC T69 °C/T79 °C Da, (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Um = 250 V
Special Conditions for Safe Use (X):
1. Potential ignition hazards by impact or friction need to be considered according to
EN 60079-0:2012 clause 8.3 (for EPL Ga and EPG Gb), and clause 8.4 (for EPL Da and
EPL Db), when the transmitter enclosure and antennas exposed to the exterior
atmosphere of the tank, is made with light metals containing aluminium or
titanium. The end user shall determine the suitability with regard to avoid hazards
from impact and friction.
2. Parts of the sensor probes, for type 5300 are non-conducting material covering
metal surfaces. The area of the non-conducting part exceeds the maximum
permissible areas for Group III according to EN 60079-0.2012 clause 7.4:3.
Therefore, when the probe is used in a potentially explosive atmosphere group III,
EPL Da, appropriate measures must be taken to prevent electrostatic discharge.
3. 1/2” NPT threads need to be sealed for dust and water ingress protection, IP 66, IP
67 or “Ex t”, EPL Da or Db is required.
B.7.2
I1 ATEX Intrinsic Safety
Certificate
Nemko 04ATEX1073X
Standards
EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN
60079-26:2015, EN 60079-31:2014
Markings
II 1G Ex ia IIC T4 Ga, (-55 °C ≤ Ta ≤ +60 °C/+70 °C)
Product certifications Reference Manual
April 2019 00809-0100-4530
362 Rosemount 5300 Level Transmitter