6.2 Using the display panel
The Rosemount
™
5300 Level Transmitter uses an optional display panel for presentation of
measurement data. When the transmitter is switched on, the display panel presents
information such as transmitter model, measurement frequency, software version,
communication type (HART
®
, FF), serial number, HART identification tag, setting of write
protection switch, and Analog Output settings.
When the transmitter is up and running, the display panel presents level, signal amplitude,
volume, and other measurement data depending on the display panel configuration (see
Specify display panel variables). The available LCD parameters are listed in Table 6-1.
The display has two rows, the upper row shows the measurement value and the lower row
shows the parameter name and measurement unit. It toggles between the different
measurement values every two seconds. The lower row toggles between parameter name
and measurement unit each second.
Variables to be presented are configurable by using a handheld communicator, AMS
Device Manager, DeltaV
™
or the Rosemount Radar Master software.
Figure 6-1: The Rosemount 5300 Level Transmitter Display Panel
A. Measurement value
B. Toggling between measurement parameter and measurement unit
Error messages are listed in LCD error messages.
Table 6-1: LCD Parameters and Presentation on Display
Parameter Presentation on display Description
Level LEVEL Product level
Distance DIST Distance from the upper
reference point to the product
surface
Level rate LRATE The speed of level movement
up or down
Signal strength AMPL The signal amplitude of the
surface echo
Volume VOUME Total product volume
Internal temperature INTEMP Temperature inside the
transmitter housing
Operation Reference Manual
April 2019 00809-0100-4530
160 Rosemount 5300 Level Transmitter