Figure D-1: Specify Upper Reference Point Using Distance Offset Parameter
A. Upper Reference Point
B. Tank Height
C. Distance Offset
D. Transmitter Reference Point
E. Product Level
Procedure
1. Adjust the Tank Height to the distance from the tank bottom to the desired Upper
Reference Point.
2. Add the distance between the Upper Reference Point and the Transmitter
Reference Point to the Distance Offset value that is stored in the transmitter
database.
a) In Rosemount Radar Master, select Setup → Tank.
b) Select the Geometry tab.
c) Click the Advanced button for more options.
d) In the Distance Offset (G) box, type the desired value.
D.3 Probe end projection
Probe End Projection is used for two purposes:
• Use the probe end echo as reference, in case the surface echo is lost, to calculate the
surface echo position.
Advanced configuration Reference Manual
April 2019 00809-0100-4530
398 Rosemount 5300 Level Transmitter