Table 7-8: Error Messages Displayed on the Rosemount 5300 Display Panel (continued)
Error message Description
FPROM FAIL An error in the gauge program memory (FPROM) has
been detected during the startup tests.
Note
This resets the gauge automatically.
HREG FAIL An error in the transmitter configuration memory
(EEPROM) has been detected. The error is either a
checksum error that can be solved by loading the default
database, or a hardware error.
Note
The default values are used until the problem is solved.
OMEM FAIL Other memory failure.
MWM FAIL An error in the microwave module.
DPLY FAIL An error in the LCD.
MODEM FAIL Modem hardware failure.
AOUT FAIL An error in the Analog Out Module.
OHW FAIL An unspecified hardware error has been detected.
ITEMP FAIL An error in the internal temperature measurement.
MEAS FAIL A serious measurement error has been detected.
CONFIG FAIL At least one configuration parameter is outside the
allowed range.
Note
The default values are used until the problem is solved.
SW FAIL An error has been detected in the transmitter software.
For more information on errors, see Errors.
7.4 LED error messages
For Rosemount 5300 Level Transmitters without display, a flashing Light Emitting Diode
(LED) is used for presentation of error messages.
Service and troubleshooting Reference Manual
April 2019 00809-0100-4530
178 Rosemount 5300 Level Transmitter