Table K-5: Output Variables for Floating Point Format Code 3
Register Name Register Number Note
Slave 1 Status 2200 Bit information in bitfield:
Bit 0: Invalid Measurement
Slave 1 PV.
Bit 1: Invalid Measurement
Slave 1 SV.
Bit 2: Invalid Measurement
Slave 1 TV.
Bit 3: Invalid Measurement
Slave 1 FV.
Bit 14: HART bus busy (slave in
burst or other master present)
Bit 15: HTM Task not running
(option not available).
Note
Bit 1-3 is set when Invalid
Measurement of Slave 1 Non
PV, i.e. all three bits are set
simultaneously.
Slave 1 PV
2202 Primary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 3.
Slave 1 SV 2204 Secondary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 3.
Slave 1 TV 2206 Tertiary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 3.
Slave 1 FV (QV) 2208 Fourth variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 3.
K.5 Specific Modbus
®
host configuration
The Remote Terminal Unit needs to be configured to communicate and correctly interpret
data when reading input registers from the Rosemount 5300 Level Transmitter.
Baud rate
The specified Baud Rates below are recommendations. If other Baud Rates are used, make
sure the Rosemount 5300 Level Transmitter and the RTU are configured for the same
communication speed.
Rosemount 5300 with HART
®
to Modbus
®