7.2 Diagnostic messages
7.2.1 Device status
Device status messages that may appear on the Integral Display, on the handheld
communicator, or in Rosemount Radar Master are shown in Table 7-1:
Table 7-1: Device status
Message Description Action
Running Boot Software The application software could not be
started.
Contact Emerson Service Department.
Device Warning A device warning is active. See Warning Messages for details.
Device Error A device error is active. See Error Messages for details.
Sim Mode 0 Active The simulation mode is active. Turn off the simulation mode in
Rosemount Radar Master, select Tools,
Simulation Mode, and click the Stop
button.
Advanced Simulation Mode
Active
The advanced simulation mode is active. To turn off the Advanced Simulation
mode, set Holding Register 3600=0 (see
View/edit holding registers).
Interface Invalid The interface measurement is invalid. Check the Error Messages, Warning
Messages, and the Interface Status for
details.
Invalid Measurement The level measurement is invalid. Check Error Messages, Warning
Messages, and Measurement Status for
details.
User Register Area Write
Protected
The configuration registers are write
protected.
Use the Lock/Unlock function to turn off
the write protection (see Write
protection).
Write Protected Jumper Set Write protection jumper on the display is
enabled.
Remove the write protection jumper.
Factory Settings Used The factory default configuration is used. The transmitter has lost its calibration.
Contact Emerson Service Department.
Probe missing Probe is not detected. Check that the probe is correctly
mounted. Check the connection between
probe and transmitter head.
7.2.2 Errors
Error messages that may be displayed on the Integral Display, on a handheld
communicator, in AMS Device Manager, or in Rosemount Radar Master are shown in Table
7-2. Errors normally result in Analog Output alarm.
Errors are indicated in Rosemount Radar Master in the Diagnostics window.
Reference Manual Service and troubleshooting
00809-0100-4530 April 2019
Reference Manual 171